homepage  Research  Publications  2006
 
Ji J, Yang R, Sun ZH, Yuan HY (2006) (Science Press USA Inc: Monmouth Junction) 721-724
Date: 2011-08-17   Author: SKLFS  ,   Source: WOS  ,
 

Ji J, Yang R, Sun ZH, Yuan HY (2006) 'Validation and evaluation of large eddy simulation based field-zone model for smoke movement in building fires.' (Science Press USA Inc: Monmouth Junction) 721-724

Web link:

Keywords:

building fire锛�/SPAN>field model锛�/SPAN>zone mode锛�/SPAN>large eddy simulation(LES),

Abstract: A Large Eddy Simulation (LES) based Field-Zone code LFZ is evaluated by comparing with the results of BRI2 (zone model), CFAST (zone model) and a full three-dimensional Large Eddy Simulation (FDS, field model). In LFZ code, the flow field in the fire room is numerically computed by the filtered three dimensional compressible Navier-Stokes equations under low-Mach number approximation by finite difference method. A volume-conservation pressure correction method based zone model is employed to compute the smoke movement in rooms without the fire source. It shows that the simulated results of new LFZ model are very close to the results of FDS, and the LFZ model can give more reasonable results than the other two models. With a view toward practical application to simulations conducted as a part of the fire safety planning, the results are promising.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176