homepage  Research  Publications  2006
 
Xie QY, Zhang HP, Zheng X (2006) (Science Press USA Inc: Monmouth Junction) 654-658
Date: 2011-08-17   Author: SKFLS  ,   Source: WOS  ,
 

Xie QY, Zhang HP, Zheng X (2006) 'Theoretical and experimental studies on heat transfer of overheated cables.' (Science Press USA Inc: Monmouth Junction) 654-658

Web link:

Keywords:

cable systems, over heated, auto-alarm monitoring, heat transfer model, fire detection,

Abstract: Fire disasters of the widely used cable systems will bring great loss and damage to the industries. The objective of this paper is to analyze the detailed heat transfer of the over heated cables and to propose a convenient monitoring technology for cable systems. The theoretical analyses are conducted for over heated three-core cables with the cross section area 95, 240 and 630 mm(2), respectively. Some corresponding experimental measurements are also carried out for the cables with a simulated over heated joint using an electric heater. Finally, the influence of the environmental temperatures on the heat transfer of the over heated cable is analyzed. It is shown that the experimental results match well the theoretical results. The results also indicate that the temperature rise on cable surface is an effective alarm criterion for the auto-alarm monitoring system no matter in cold winter or in hot summer. An auto-alarm monitoring system based on the heat transfer model was successfully used for the cable system in the Anqin Petroleum and Chemical Corporation.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176