L. Li, X. J. Huang, K. Bi and X. S. Liu (2016) Nuclear Engineering And Design 301 32-38. |
|
|
Date: 2017-03-13
Author: SKLFS  , Source: SKLFS  ,
|
|
L. Li, X. J. Huang, K. Bi and X. S. Liu (2016) An enhanced fire hazard assessment model and validation experiments for vertical cable trays. Journal/Nuclear Engineering And Design 301 32-38. [In English] Web link: http://dx.doi.org/10.1016/j.nucengdes.2015.12.034 Keywords: ELECTRIC CABLES Abstract: The model, referred to as FLASH-CAT (Flame Spread over Horizontal Cable Trays), was developed to estimate the heat release rate for vertical cable tray fire. The focus of this work is to investigate the application of an enhanced model to the single vertical cable tray fires with different cable spacing. The experiments on vertical cable tray fires with three typical cable spacing were conducted. The histories of mass loss rate and flame length were recorded during the cable fire. From the experimental results, it is found that the space between cable lines intensifies the cable combustion and accelerates the flame spread. The predictions by the enhanced model show good agreements with the experimental data. At the same time, it is shown that the enhanced model is capable of predicting the different behaviors of cable fires with different cable spacing by adjusting the flame spread speed only. (C) 2016 Elsevier B.V. All rights reserved.
|
|
|
|
|
|
|
|
|
|
|
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026 |
|
|
|
Tel:(+86)551 63601651 |
|
Fax:(+86)551 63601669 |
|
E-mail:sklfs@ustc.edu.cn |
|
|
|
|
|