homepage  Research  Publications  2016
 
Y. Q. Chen, X. D. Zhou, T. L. Zhang, Z. J. Fu, Y. Q. Hu and L. Z. Yang (2016) International Journal Of Numerical Methods for Heat & Fluid Flow 26 1684-1698.
Date: 2017-03-08   Author: SKLFS  ,   Source: SKLFS  ,
 

Y. Q. Chen, X. D. Zhou, T. L. Zhang, Z. J. Fu, Y. Q. Hu and L. Z. Yang (2016) Numerical analysis of combined buoyancy-induced and pressure-driven smoke flow in complex vertical shafts during building fires. Journal/International Journal Of Numerical Methods for Heat &, Fluid Flow 26 1684-1698. [In English]
Web link: http://dx.doi.org/10.1108/hff-11-2014-0355
Keywords: ,Building fires, Hot smoke flow, Neutral pressure plane, Smoke control, Vertical shafts, COMPARTMENT FIRE, MODEL, MOVEMENT, SPACE, AIR, VENTILATION, CONVECTION, FLUID

Abstract: Purpose - The purpose of this paper is to study the behavior of smoke flow in building fires and optimize the design of smoke control systems. Design/methodology/approach - A total of 435 3-D fire simulations were conducted through NIST fire dynamics simulator to analyze thermal behavior of combined buoyancy-induced and pressure-driven smoke flow in complex vertical shafts, under consideration of influence of heat release rate (HRR) and locations of heat sources. This influence was evaluated through neutral pressure plane (NPP), which is a critical plane depicting the flow velocity distributions. Hot smoke flows out of shafts beyond the NPP and cold air flows into shafts below the NPP. Findings - Numerical simulation results show that HRR of heat source has little influence on NPP, while location of heat source can make a significant difference to NPP, particularly in cases of multi-heat source. Identifying the location of NPP helps to develop a more effective way to control the smoke with less energy consumption. Through putting an emphasis on smoke exhausting beyond the NPP and air supplying below the NPP, the smoke control systems can make the best use of energy. Research limitations/implications - Because of the chosen research approach, the research results may need to be tested by further experiments. Practical implications - The paper includes implications for the optimization of smoke control systems design in buildings. Originality/value - This paper fulfills an identified need to research the behavior of hot smoke in building fires and optimize the design of smoke control systems.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176