homepage  Research  Publications  2016
 
Z. G. Wu, L. Z. Yang, J. Zhan, Y. Q. Chen, X. D. Zhou, Y. Q. Hu, A. A. Stec and T. R. Hull (2016) Fire And Materials 40 18-26.
Date: 2017-03-08   Author: SKLFS  ,   Source: SKLFS  ,
 

Z. G. Wu, L. Z. Yang, J. Zhan, Y. Q. Chen, X. D. Zhou, Y. Q. Hu, A. A. Stec and T. R. Hull (2016) Experimental study on polystyrene with intumescent flame retardants from different scale experiments. Journal/Fire And Materials 40 18-26. [In English]
Web link: http://dx.doi.org/10.1002/fam.2251
Keywords: ,IFR, intumescent flame retardant, polystyrene composites, flammability, toxicity, THERMAL-DEGRADATION, EPOXY-RESINS, CALORIMETRY

Abstract: In this study, the fire performance and toxicity of intumescent flame retardant (IFR) polystyrene composites were investigated experimentally. Ammonium polyphosphate, pentaerythritol, and melamine were selected as IFR. The flammability of the polystyrene (PS) composites was evaluated by microscale combustion calorimetry and cone calorimetry and in the ISO Room. The results suggested that the thermal stability and the peak heat release rate of PS composites decreased with the increasing content of IFR. In the cone calorimeter and ISO 9705 testing, the carbon monoxide yield of PS composites also decreased markedly with the addition of IFR. Scanning electron microscope images show that the char from cone calorimetry testing was more compact and smoother than that from the ISO 9705 testing. The comparison between bench- and full-scale tests demonstrated that the flammability and the toxicity of PS composites are decreased markedly due to the incorporation of the flame retardant, but considerable differences exist. Copyright (c) 2014 John Wiley &, Sons, Ltd.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176