homepage  Research  Publications  2015
 
Z. H. Gao, J. Ji, C. G. Fan and J. H. Sun (2015) International Journal Of Heat And Mass Transfer 84 262-270.
Date: 2016-03-01   Author: SKLFS  ,   Source: SKLFS  ,
 

Z. H. Gao, J. Ji, C. G. Fan and J. H. Sun (2015) Experimental analysis of the influence of accumulated upper hot layer on the maximum ceiling gas temperature by a modified virtual source origin concept. Journal/International Journal Of Heat And Mass Transfer 84 262-270. [In English]
Web link: http://dx.doi.org/10.1016/j.ijheatmasstransfer.2015.01.006
Keywords: Maximum temperature, Transverse location, Heat release rate, Sidewall, Ceiling, Thermal flow, ROAD TUNNEL FIRES, LONGITUDINAL VENTILATION, SMOKE, WALL, PLUMES, CORNER, FLOW
Abstract: This paper presents an experimental investigation to explore the influence of an accumulated hot upper layer on the maximum ceiling gas temperature of buoyancy-driven thermal flow in a reduced scale tunnel model. Experimental results show that the maximum excess temperature changes small with the decreasing of distance between fire source and the nearest sidewall until fire is flush with sidewall, then the maximum ceiling gas temperature increases significantly. A modified concept of virtual origin is introduced for calculating the maximum ceiling gas temperature in the presence of a hot upper layer beneath ceiling. On the basis of the experimental data and theoretical analysis, correlations of the virtual source location are proposed for fire placed out of touch and flush with sidewall, respectively. Further, the predicted maximum ceiling gas temperatures are compared with the measured ones for fire out of touch with sidewall as well as the data from other model-scale and full-scale tests. The results show that there is a good agreement when the modified dimensionless heat release rate, Q(mod), which expresses the relative size of beat release rate compared to the tunnel geometry, is smaller than 0.09, otherwise the predicted maximum temperatures will be lower than the experimental values because of the impingement of intermittent flame on the tunnel ceiling. (C) 2015 Elsevier Ltd. All rights reserved.


 ,

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176