homepage  Research  Publications  2005
 
Yao B, Chow WK (2005) International Journal of Thermal Sciences 44(4), 410-419.
Date: 2011-08-17   Author: SKLFS  ,   Source: WOS  ,
 

Yao B, Chow WK (2005) Extinguishment of a PMMA fire by water spray with high droplet speeds. International Journal of Thermal Sciences 44(4), 410-419. [In English]

Web link:http://dx.doi.org/10.1016/j.ijthermalsci.2004.06.006

Keywords:

water spray, PMMA, fire extinguishment, thermal model, critical fraction,

Abstract: A thermal model was developed to study the extinguishment of a polymethyl methacrylate (PMMA) fire by water spray with droplet speeds high enough to travel through the plume and the flaming region. Suppression mechanisms involving fuel surface cooling, flame cooling and oxygen displacement were considered. The critical fraction of total heat released that was transferred back to the fuel surface was taken as the critical condition for solid fire extinguishment. The effects of droplet size and velocity, external radiant heat flux and specimen configuration on fire suppression were investigated. The results indicate that larger droplets would reach the fuel surface and surface cooling would play a dominating role. Smaller droplets would absorb heat from the flame and evaporate to reduce the critical fraction of total heat released at extinction as a flame extinguishing agent. This might result in a critical water application rate, above which the flame can no longer be sustained even under a high external heat flux as in real fires. Therefore, spray containing a variety of droplet sizes would perform better than a uniform spray in extinguishing PMMA fires under a high external radiant heat flux. (c) 2004 Elsevier SAS. All rights reserved.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176