Zhong MH, Li PD, Liu TM, Wei X, Liao GX (2005) Experimental study on fire smoke movement in a multi-floor and multi-room building. Science in China Series E-Engineering &, Materials Science 48(3), 292-304. [In English]

Web link:http://dx.doi.org/10.1360/04ye0050

Keywords:

multi-floor and multi-room, fire experiment, smoke spread, smoke, toxicity, flashover, model,

Abstract: Fire smoke movement of multi-floor and multi-room (MFMR) fire was studied at the model test building in State Key Laboratory of Fire Science (SKLFS). The ingredient, temperature, air pressure difference and air velocity of smoke were measured and analyzed. Meanwhile, the hazard of smoke ingredient to exposed occupants was analyzed based on the national standard, Occupational Exposure Limit for Hazardous Agents in the Workplace (GBZ2-2002). The experimental results showed that the maximum temperature difference in MFMR fire was located along the vertical height from the fire source. With the spreading and diffusion of smoke, the temperature of smoke layer would tend to be no difference. In the fire of woodpile and kerosene, the main smoke ingredients such as SO2, CO and CO2 would first exceed human's average physiological limit, while smoke ingredients such as NO and NO2 would come behind. Because of the higher fluctuation range and frequency of air pressure difference of smoke in multi-layer building fire, the fire smoke would spread around everywhere of the passageway and made the human evacuation more difficult.

 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176