homepage  Research  Publications  2009
 
Cong BH, Liao GX, Huang Z (2009) Journal of Fire Sciences 27(1), 5-26.
Date: 2011-08-16   Author: SKLFS  ,   Source: WOS  ,
 

Cong BH, Liao GX, Huang Z (2009) Extinction Limit of Diesel Pool Fires Suppressed by Water Mist. Journal of Fire Sciences 27(1), 5-26. [In English]

Web link: http://dx.doi.org/10.1177/0734904108095337

Keywords:

water mist, diesel pool fires, extinction limit, fire suppression and, intensification, sprays

Abstract: This work describes an experimental and theoretical investigation of extinction limit of diesel pool fires suppressed by water mist. A downward-directed nozzle produced a fine water spray over small-scale opposed diesel pool fires. The fire extinction limit is obtained from minimum nozzle injection pressure or maximum fire size when the fire extinguishment took place. For the conditions tested, it is observed that there are two distinct regions in the relationship between the injection pressure and fire size, i.e., a fire suppression region and a fire intensification region. The transition of the two regions is dependent on the effective water flux and the plume-spray thrust ratio. It is also revealed that the fuel surface cooling is the dominant mechanism for diesel pool fires at extinction limit in the tests. The failure to cause fire extinction is mainly due to the insufficient water flux applied to remove enough heat from the fuel surface.
 
Print    Close
 
 
   
  
 
Relevant link
Contact us
State Key Laboratory of Fire Science, University of Science and Technology of China
Jinzhai Road 96, Hefei, Anhui, P. R. China
P. O.: 230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
 
 
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
Tel:(+86)551 3601651 | Fax:(+86)551 3601669 | E-mail:sklfs@ustc.edu.cn | ICP: D20380176